InlineFansFAQ-QA5

Jul 10, 2018, 22:19 PM
Can inline vane axial fans be used for high temperature exhaust?
Link text :
Select a Card/Question Answer : QuestionAnswer
Display order : 5

Typical applications for inline vane axial fans involve exhausting or supplying clean, ambient air. Greenheck's recommendation for continuous high temperature operation is 43° C (110° F) for direct drive vane axials, where the motor is in the airstream, and 93° C (200° F) for belt drive vane axials, where the motor is out of the airstream.

For emergency smoke ventilation involving temperatures above 200° F, please contact us.